Strong Engineering Support
Our technical team supports product selection, parameter confirmation, structure discussion and project requirement analysis for power distribution applications.
The S13 series are fully sealed oil-immersed transformers suitable for power systems with an AC frequency of 50Hz and a rated working voltage of 20kV or less. They are used as distribution transformers in enterprises such as petroleum, metallurgy, chemical engineering, textile, and light industry, as well as in places with large amounts of dust. The transformers feature a high-reliability core made of high-permeability grain-oriented cold-rolled silicon steel sheet, an advanced insulation system, and a fully sealed oil tank design, ensuring maintenance-free operation and a long service life.
The S13 series are fully sealed oil-immersed power distribution transformers designed for AC systems with a rated frequency of 50Hz and a maximum working voltage of 20kV. They are primarily used as distribution transformers in various industrial enterprises, including the petroleum, metallurgy, chemical engineering, textile, and light industry sectors, as well as in locations with high levels of dust. The transformers are designed for high efficiency, low loss, and reliable operation, making them suitable for both indoor and outdoor installations (outdoor installation requires direct sunlight, corrosive gases, or dust to be avoided, while indoor installation requires sufficient heat dissipation space and safety distance).
1.Core: The core is made of high-permeability grain-oriented cold-rolled silicon steel sheet. It adopts a new-type structure with fully mitered lap stacked core. The core limb features a multi-step stepped circular cross-section, and the yoke has an equal cross-section to the core limb, ensuring high magnetic efficiency and low no-load loss.
2.Winding: The windings are designed with corrugated oil ducts, adopting a non-varnish impregnation process and fastened with binding tapes. All windings are concentric coils. The high-voltage winding is equipped with taps corresponding to the required tap voltages, which are connected to the tap changer. The tap changer is mounted on the tank cover, and tap voltage adjustment can only be performed after power off.
3.Safety Protection Devices: Transformers with a capacity of 30-2000 kVA are fitted with a pressure relief valve. A gas relay with alarm and trip terminals can be installed according to user requirements.
4.Oil Temperature Measuring Device: All transformers are equipped with a socket for a glass thermometer, which is installed on the top of the oil tank and extends into the oil at a depth of 120±10 mm. Transformers with a capacity of 1000-2000 kVA are fitted with an outdoor-type signal thermometer.
5.Transformer Tank: The transformer tank is constructed with corrugated walls, and its surface is treated with powder coating for firm paint adhesion. The corrugated walls serve the dual functions of heat dissipation and “breathing” fluctuations in volume changes of the transformer oil caused by temperature fluctuations. As a result, the fully sealed transformer eliminates the need for an oil conservator, reducing the overall height of the unit. Vacuum oil filling is applied during transformer encapsulation to completely remove moisture inside the transformer. The transformer oil is isolated from air contact, effectively preventing oxygen and moisture ingress that would degrade insulation performance and accelerate oil aging. Therefore, regular oil sample testing is not required.
6.Working Conditions: Suitable for areas with an altitude not exceeding 1,000 meters, a maximum ambient temperature of +40°C, and a minimum ambient temperature of -25°C or -5°C. The rated frequency of the connected power grid is 50Hz, and the fluctuation range of the power supply voltage shall not exceed ±5% of the rated voltage. The waveform distortion rate shall meet the harmonic management requirements of the power system. The transformers can be installed outdoors or indoors in well-ventilated places. For outdoor installation, direct sunlight, corrosive gases, or dust accumulation shall be avoided; for indoor installation, sufficient heat dissipation space and safety distance shall be ensured. The transformer is allowed to operate continuously for a long time under rated capacity and has a certain short-time overload capacity. If used in special environments such as thunderstorm-prone areas, high humidity, heavy pollution, chemical corrosion, or seismic zones, prior notification shall be given, and an enhanced protection scheme shall be provided.
| Rated Capacity (kVA) |
High voltage (KV) |
High voltage tapping range (%) |
Low voltage (kV) |
S13-M | No load current (%) |
Short-circuit impedance% |
||
| electrical strip steel | ||||||||
| No load loss kW | Full load loss kW | |||||||
| Dyn11/Yzn11 | Yyno | |||||||
| 30 | 63 10 10.5 |
±2×2.5 ±5 |
0.4 | 80 | 630 | 710 | 1.2 | 4 |
| 50 | 100 | 910 | 100 | 1.04 | ||||
| 63 | 110 | 1090 | 1380 | 0.96 | ||||
| 80 | 130 | 1310 | 1380 | 0.96 | ||||
| 100 | 150 | 1580 | 1570 | 0.88 | ||||
| 125 | 170 | 1890 | 1850 | 0.88 | ||||
| 160 | 200 | 2310 | 2130 | 0.8 | ||||
| 200 | 240 | 2730 | 2530 | 0.8 | ||||
| 250 | 290 | 3200 | 2760 | 0.72 | ||||
| 315 | 340 | 3830 | 3470 | 0.72 | ||||
| 400 | 410 | 4520 | 3990 | 0.64 | ||||
| 500 | 480 | 5410 | 4880 | 0.64 | ||||
| 630 | 570 | 6200 | 0.48 | 4.5 | ||||
| 800 | 700 | 7500 | 0.48 | |||||
| 1000 | 830 | 10300 | 0.48 | |||||
| 1250 | 970 | 12000 | 0.4 | |||||
| 1600 | 1170 | 14500 | 0.4 | |||||
| 2000 | 1360 | 18300 | 0.32 | 5 | ||||
| 2500 | 1600 | 21200 | 0.32 | |||||

Customized transformers, switchgear, ring main units, prefabricated substations and electrical components for project requirements, technical specifications and market applications.
Our technical team supports product selection, parameter confirmation, structure discussion and project requirement analysis for power distribution applications.
We provide flexible configuration support for transformers, switchgear, ring main units, prefabricated substations and related electrical components.
With continuous improvement in production equipment, process management and quality control, Shenheng Power supports stable customized manufacturing.
From early communication to production follow-up and after-sales support, we provide responsive service for customers and project partners.
Real production environments behind consistent quality and dependable project delivery.
Power distribution solutions serving industrial, commercial and infrastructure projects.
Empowering the Backbone of Modern Infrastructure Modern utility grids face unprecedented challenges: increasing energy demand, aging infrastructure, and the need...
View More
Driving the Transition to a Sustainable Future The shift towards renewable energy requires electrical infrastructure that can handle fluctuating power...
View More
Powering Heavy Industry with Uncompromising Reliability In industrial manufacturing, metallurgy, and mining, power interruptions mean halted production lines, damaged materials,...
View More
Delivering Safe and Silent Power to Urban Centers Large commercial buildings, hospitals, airports, and shopping malls require highly reliable power...
View More
Accelerating the E-Mobility Revolution The rapid expansion of electric vehicles (EVs) requires a massive rollout of fast-charging stations. These stations...
View More
Securing Power for the Digital Economy In the digital age, data is the most valuable asset. Data centers and telecom...
View More