{"id":3148,"date":"2026-11-02T18:20:35","date_gmt":"2026-11-02T10:20:35","guid":{"rendered":"https:\/\/shenhengglobal.com\/?p=3148"},"modified":"2026-11-05T14:09:00","modified_gmt":"2026-11-05T06:09:00","slug":"transformer-factory-test-dissolved-gas-analysis","status":"publish","type":"post","link":"https:\/\/shenhengglobal.com\/ja\/blog\/transformer-factory-test-dissolved-gas-analysis\/","title":{"rendered":"\u5909\u5727\u5668\u5de5\u5834\u8a66\u9a13DGA\uff1a\u524d\u5f8c\u306e\u8a3c\u62e0"},"content":{"rendered":"<p>Transformer factory test dissolved gas analysis compares identified oil samples taken around an agreed electrical or thermal test sequence. Its purpose is to help assess whether that sequence produced gas evidence requiring investigation before acceptance. It is not interchangeable with an in-service DGA alarm chart. A useful review matches the transformer, sample timing, oil processing history, laboratory method and contractual decision rule. Without that context, a before-and-after difference can be misleading even when both laboratory reports are technically valid.<\/p>\n<h2>Define the acceptance question before taking samples<\/h2>\n<p>Start by identifying the test or sequence being assessed. A factory may perform several activities between oil filling and shipment, and the term \u201cafter test\u201d is not precise enough. Record the actual event, completion time and sampling plan. The project should establish who reviews the gas data, which requirements apply and what happens if the results are unexpected. Agreeing these items beforehand prevents selective interpretation after a result is known.<\/p>\n<p>The public listing for <a href=\"https:\/\/webstore.iec.ch\/en\/publication\/4768\" rel=\"noopener nofollow\" target=\"_blank\">IEC 61181<\/a> identifies the dedicated subject of factory-test DGA for mineral-oil-filled electrical equipment. Verify the applicable publication and edition in the contract rather than quoting unavailable clauses. The <a href=\"https:\/\/www.usbr.gov\/tsc\/techreferences\/mands\/mands-pdfs\/Trnsfrmr.pdf\" rel=\"noopener nofollow\" target=\"_blank\">US Bureau of Reclamation transformer manual<\/a> supplies broader DGA context for maintenance. It should not be used to turn a service interpretation category into a universal factory acceptance threshold.<\/p>\n<h2>Keep this review separate from service fault diagnosis<\/h2>\n<p>In-service DGA often examines trends over operating time, loading and thermal history. Factory testing concerns a defined event on equipment with a different history. Oil can have been treated, transferred, circulated or replaced shortly before sampling. Residual gas and the sampling sequence can therefore affect the comparison. A reviewer should establish the baseline circumstances before assigning meaning to a gas increment or ratio.<\/p>\n<p>The same named gas can be relevant in several contexts, but its significance depends on the complete evidence. Do not copy an online alarm table into a purchase specification without engineering review. Use our <a href=\"https:\/\/shenhengglobal.com\/blog\/transformer-dissolved-gas-analysis\/\">in-service transformer DGA guide<\/a> for the separate diagnostic topic. This article focuses on traceable factory acceptance records and the questions a buyer can reasonably ask before releasing the transformer.<\/p>\n<figure><img decoding=\"async\" alt=\"Shenheng oil-immersed transformer with a conservator and external radiators\" class=\"wp-image-3321\" height=\"1024\" loading=\"lazy\" src=\"https:\/\/shenhengglobal.com\/wp-content\/uploads\/2026\/11\/shenheng-product-only-20261105-3148-body-1.webp\" width=\"1536\" srcset=\"https:\/\/shenhengglobal.com\/wp-content\/uploads\/2026\/11\/shenheng-product-only-20261105-3148-body-1.webp 1536w, https:\/\/shenhengglobal.com\/wp-content\/uploads\/2026\/11\/shenheng-product-only-20261105-3148-body-1-300x200.webp 300w, https:\/\/shenhengglobal.com\/wp-content\/uploads\/2026\/11\/shenheng-product-only-20261105-3148-body-1-1024x683.webp 1024w, https:\/\/shenhengglobal.com\/wp-content\/uploads\/2026\/11\/shenheng-product-only-20261105-3148-body-1-768x512.webp 768w, https:\/\/shenhengglobal.com\/wp-content\/uploads\/2026\/11\/shenheng-product-only-20261105-3148-body-1-18x12.webp 18w, https:\/\/shenhengglobal.com\/wp-content\/uploads\/2026\/11\/shenheng-product-only-20261105-3148-body-1-1000x667.webp 1000w\" sizes=\"auto, (max-width: 1536px) 100vw, 1536px\" \/><figcaption>Product-reference illustration based on <a href=\"https:\/\/shenhengglobal.com\/product\/35kv-mvhv-oil-immersed-industrial-custom-power-transformer\/\">Shenheng Oil Immersed Transformer<\/a>. Setting is illustrative; this is not a photograph of an actual test or operation.<\/figcaption><\/figure>\n<h2>Build an event timeline that the laboratory can use<\/h2>\n<p>The timeline should connect oil treatment, filling, relevant tests, circulation or settling periods, sampling and dispatch. Use actual timestamps with an identified time zone. Identify any intervention between the samples, including topping up or additional degassing. If two laboratories participated, record when each received its sample and which handling instructions applied. A simple chronology often explains an apparent inconsistency more effectively than an isolated gas table.<\/p>\n<p>Keep sample locations consistent with the approved plan. A sample drawn from a different compartment cannot automatically stand in for the original location. Note the valve or point identifier and any separate oil volume. The sampling team should follow the agreed method and safety procedure; this article does not provide a field sampling operation. Equipment identity and sample traceability are essential whether the project uses a small distribution unit or a larger industrial transformer.<\/p>\n<h2>Use a comparison table with context<\/h2>\n<div style=\"overflow-x:auto\">\n<table>\n<thead>\n<tr>\n<th>Evidence<\/th>\n<th>Before-test record<\/th>\n<th>After-test record and review<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>Equipment and sample identity<\/td>\n<td>Serial number, compartment, sample ID<\/td>\n<td>Same equipment and intended comparison point<\/td>\n<\/tr>\n<tr>\n<td>Event timing<\/td>\n<td>Oil treatment and sampling timestamps<\/td>\n<td>Test completion and sampling timestamps<\/td>\n<\/tr>\n<tr>\n<td>Laboratory method<\/td>\n<td>Method revision, units, reporting limits<\/td>\n<td>Same basis or documented method difference<\/td>\n<\/tr>\n<tr>\n<td>Intervening work<\/td>\n<td>Initial filling and processing state<\/td>\n<td>Top-up, circulation, treatment or other changes<\/td>\n<\/tr>\n<tr>\n<td>Decision<\/td>\n<td>Approved baseline and requirements<\/td>\n<td>Engineering interpretation and deviation closure<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<\/div>\n<p>The table intentionally contains no generic gas limits. Use the requirements in the applicable standard, approved specification and engineering assessment. Preserve the original laboratory reports alongside any summary. A spreadsheet that drops qualifiers or changes units can create a false impression of precision and make a later investigation difficult to reproduce.<\/p>\n<h2>Calculate differences without inventing significance<\/h2>\n<p>For a gas reported on the same concentration basis, an arithmetic difference is the after value minus the before value. Suppose a purely illustrative report lists 12 units before and 17 units after, with the units and method genuinely identical. The arithmetic increase is 5 units. That calculation alone does not establish whether the change is significant, unacceptable or caused by the test. Laboratory uncertainty, reporting limits, sampling variation and equipment history still matter.<\/p>\n<p>Results reported below a detection or quantification limit require particular care. A less-than result is not an exact zero and should not be silently replaced by zero in a percentage-change calculation. Ask the laboratory how it recommends treating censored data. Keep the original qualifier visible in the summary. A small baseline can also make a percentage change appear dramatic while the absolute difference remains small and uncertain.<\/p>\n<h2>Check method comparability before interpreting a pattern<\/h2>\n<p>Ask whether extraction technique, analytical method, calibration basis and reported gas list are consistent. A change of laboratory does not automatically invalidate a comparison, but it introduces questions that should be answered. Request the method identifiers and any documented equivalence or comparability assessment. Accreditation should be checked for the relevant scope rather than treated as proof that every possible oil test is covered.<\/p>\n<p>Discuss unusual results with the laboratory and transformer manufacturer together. Request an explanation of possible sample or method issues before deciding whether additional testing is necessary. If repeat samples are approved, identify exactly what the repeat is meant to resolve. Repeatedly testing without a defined question can consume the available sample and produce more numbers without improving the acceptance decision.<\/p>\n<figure><img decoding=\"async\" alt=\"Shenheng oil-immersed transformer with a conservator and panel radiators\" class=\"wp-image-3322\" height=\"1024\" loading=\"lazy\" src=\"https:\/\/shenhengglobal.com\/wp-content\/uploads\/2026\/11\/shenheng-product-only-20261105-3148-body-2.webp\" width=\"1536\" srcset=\"https:\/\/shenhengglobal.com\/wp-content\/uploads\/2026\/11\/shenheng-product-only-20261105-3148-body-2.webp 1536w, https:\/\/shenhengglobal.com\/wp-content\/uploads\/2026\/11\/shenheng-product-only-20261105-3148-body-2-300x200.webp 300w, https:\/\/shenhengglobal.com\/wp-content\/uploads\/2026\/11\/shenheng-product-only-20261105-3148-body-2-1024x683.webp 1024w, https:\/\/shenhengglobal.com\/wp-content\/uploads\/2026\/11\/shenheng-product-only-20261105-3148-body-2-768x512.webp 768w, https:\/\/shenhengglobal.com\/wp-content\/uploads\/2026\/11\/shenheng-product-only-20261105-3148-body-2-18x12.webp 18w, https:\/\/shenhengglobal.com\/wp-content\/uploads\/2026\/11\/shenheng-product-only-20261105-3148-body-2-1000x667.webp 1000w\" sizes=\"auto, (max-width: 1536px) 100vw, 1536px\" \/><figcaption>Product-reference illustration based on <a href=\"https:\/\/shenhengglobal.com\/product\/35kv-mvhv-oil-immersed-industrial-custom-power-transformer\/\">Shenheng Oil Immersed Transformer<\/a>. Setting is illustrative; this is not a photograph of an actual test or operation.<\/figcaption><\/figure>\n<h2>Relate gas evidence to the rest of the factory file<\/h2>\n<p>DGA should be read with the relevant electrical test records, observations and any deviations. If a test was interrupted or repeated, the sequence should appear in the chronology. If the factory changed an accessory or corrected a connection, establish whether that affected the oil volume or acceptance scope. A gas report should not be reviewed in isolation from the event it is supposed to help assess.<\/p>\n<p>The <a href=\"https:\/\/shenhengglobal.com\/blog\/transformer-temperature-rise-limits\/\">temperature-rise guide<\/a> explains a complementary thermal acceptance topic. The <a href=\"https:\/\/shenhengglobal.com\/blog\/transformer-induced-voltage-vs-applied-voltage-test\/\">induced and applied voltage test comparison<\/a> separates two electrical test purposes. These documents should support a coherent release package rather than be combined into a single unsupported pass statement.<\/p>\n<h2>Specify deliverables that remain useful after shipment<\/h2>\n<p>For an <a href=\"https:\/\/shenhengglobal.com\/product\/35kv-mvhv-oil-immersed-industrial-custom-power-transformer\/\">industrial oil immersed transformer<\/a>, request a serial-specific sample register, laboratory reports, relevant event timeline and the responsible engineer&#8217;s release decision. Define how the factory will document a laboratory correction or amended report. The final record should identify which revision supersedes an earlier copy and why, while preserving the original audit trail.<\/p>\n<p>Carry the accepted factory data into the commissioning file as contextual history. It may help establish what was known before transport, but it is not automatically the sole baseline for future operation. Receiving and commissioning samples may reflect subsequent treatment and handling. Use the <a href=\"https:\/\/shenhengglobal.com\/blog\/how-to-choose-the-right-oil-immersed-transformer-a-buyers-guide\/\">oil transformer purchasing guide<\/a> to align these deliverables with the overall order and assign ownership before shipment.<\/p>\n<h2>Close exceptions with an explicit decision<\/h2>\n<p>A useful exception log states the observation, affected samples, possible explanations considered, evidence requested and final disposition. Avoid vague notes such as \u201cDGA acceptable\u201d without a named reviewer or governing requirement. If uncertainty remains, the engineering release should describe the limitation and any agreed follow-up. Commercial pressure to ship does not remove the need for a defensible technical conclusion.<\/p>\n<p>Procurement teams can improve the process by asking precise questions rather than diagnosing gas patterns themselves. Confirm whether the samples are comparable, whether the requirement was met and whether unresolved issues affect release. That preserves the boundary between document review and specialist interpretation while ensuring that the delivered transformer has a usable, traceable acceptance history.<\/p>\n<h2>Example: oil processing between the two samples<\/h2>\n<p>Imagine that a baseline sample was collected before an electrical test, but the factory then processed the oil before collecting the reported final sample. Even if the final result is low, the two reports do not isolate the gas effect of the test. The processing event is part of the interpretation and must remain visible. Ask the manufacturer whether the original sampling plan was followed and what evidence supports the final acceptance decision.<\/p>\n<p>This situation does not justify inventing a corrected gas concentration. Nor should a reviewer simply discard the reports. Preserve the chronology and request an engineering explanation of what can still be concluded. If additional evidence is required, define its purpose and approval before proceeding. The resulting release note should distinguish the actual evidence from an ideal comparison that was never performed, giving future reviewers an honest account of the factory sequence.<\/p>\n<h2>Further learning: gas analysis context<\/h2>\n<p>This CIRED Malaysia educational webinar reviews transformer oil diagnostics using dissolved gas analysis. It provides analysis context; factory acceptance must still follow the agreed test sequence and applicable requirements. It is not evidence of a measured result for the pictured product.<\/p>\n<div style=\"position:relative;width:100%;aspect-ratio:16\/9\"><iframe allowfullscreen=\"\" loading=\"lazy\" src=\"https:\/\/www.youtube-nocookie.com\/embed\/bTEocWzvaCo\" style=\"position:absolute;width:100%;height:100%;border:0\" title=\"2\/12\/2021: A Review on Transformer Oil Diagnostics Using Dissolved Gas Analysis Technique\"><\/iframe><\/div>\n<p><a href=\"https:\/\/www.youtube.com\/watch?v=bTEocWzvaCo\" rel=\"noopener nofollow\" target=\"_blank\">Watch 2\/12\/2021: A Review on Transformer Oil Diagnostics Using Dissolved Gas Analysis Technique on YouTube<\/a><\/p>\n<h2>Frequently asked questions<\/h2>\n<h3>Can service DGA alarm limits be used for factory acceptance?<\/h3>\n<p>Do not substitute them automatically. Factory-test interpretation must follow the applicable contract, test context and responsible engineering assessment.<\/p>\n<h3>Does a gas increase prove that a factory test damaged the transformer?<\/h3>\n<p>No. A difference requires review of sampling, oil processing, methods, uncertainty and the complete test sequence before a cause can be assigned.<\/p>\n<h3>Should less-than results be entered as zero?<\/h3>\n<p>No. Preserve the qualifier and ask the laboratory how censored results should be handled in the intended comparison.<\/p>\n<h3>What should the buyer retain at handover?<\/h3>\n<p>Keep original laboratory reports, sample identity, event timestamps, method details, deviations and the authorized engineering release decision together.<\/p>\n<p><script type=\"application\/ld+json\">{\"@context\": \"https:\/\/schema.org\", \"@type\": \"FAQPage\", \"mainEntity\": [{\"@type\": \"Question\", \"name\": \"Can service DGA alarm limits be used for factory acceptance?\", \"acceptedAnswer\": {\"@type\": \"Answer\", \"text\": \"Do not substitute them automatically. Factory-test interpretation must follow the applicable contract, test context and responsible engineering assessment.\"}}, {\"@type\": \"Question\", \"name\": \"Does a gas increase prove that a factory test damaged the transformer?\", \"acceptedAnswer\": {\"@type\": \"Answer\", \"text\": \"No. A difference requires review of sampling, oil processing, methods, uncertainty and the complete test sequence before a cause can be assigned.\"}}, {\"@type\": \"Question\", \"name\": \"Should less-than results be entered as zero?\", \"acceptedAnswer\": {\"@type\": \"Answer\", \"text\": \"No. Preserve the qualifier and ask the laboratory how censored results should be handled in the intended comparison.\"}}, {\"@type\": \"Question\", \"name\": \"What should the buyer retain at handover?\", \"acceptedAnswer\": {\"@type\": \"Answer\", \"text\": \"Keep original laboratory reports, sample identity, event timestamps, method details, deviations and the authorized engineering release decision together.\"}}]}<\/script><\/p>\n","protected":false},"excerpt":{"rendered":"<p>\u5909\u5727\u5668\u5de5\u5834\u306e\u8a66\u9a13DGA\u3092\u3001\u524d\u5f8c\u306e\u30b5\u30f3\u30d7\u30eb\u8b58\u5225\u3001\u6cb9\u51e6\u7406\u5c65\u6b74\u3001\u65b9\u6cd5\u306e\u6bd4\u8f03\u6027\u3001\u53d7\u5165\u8a3c\u62e0\u3068\u3068\u3082\u306b\u30ec\u30d3\u30e5\u30fc\u3057\u3066\u304f\u3060\u3055\u3044\u3002.<\/p>","protected":false},"author":4,"featured_media":3320,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"_gspb_post_css":"","footnotes":""},"categories":[1],"tags":[],"class_list":["post-3148","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-blog"],"blocksy_meta":{"styles_descriptor":{"styles":{"desktop":"","tablet":"","mobile":""},"google_fonts":[],"version":7}},"acf":[],"_links":{"self":[{"href":"https:\/\/shenhengglobal.com\/ja\/wp-json\/wp\/v2\/posts\/3148","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/shenhengglobal.com\/ja\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/shenhengglobal.com\/ja\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/shenhengglobal.com\/ja\/wp-json\/wp\/v2\/users\/4"}],"replies":[{"embeddable":true,"href":"https:\/\/shenhengglobal.com\/ja\/wp-json\/wp\/v2\/comments?post=3148"}],"version-history":[{"count":5,"href":"https:\/\/shenhengglobal.com\/ja\/wp-json\/wp\/v2\/posts\/3148\/revisions"}],"predecessor-version":[{"id":3359,"href":"https:\/\/shenhengglobal.com\/ja\/wp-json\/wp\/v2\/posts\/3148\/revisions\/3359"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/shenhengglobal.com\/ja\/wp-json\/wp\/v2\/media\/3320"}],"wp:attachment":[{"href":"https:\/\/shenhengglobal.com\/ja\/wp-json\/wp\/v2\/media?parent=3148"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/shenhengglobal.com\/ja\/wp-json\/wp\/v2\/categories?post=3148"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/shenhengglobal.com\/ja\/wp-json\/wp\/v2\/tags?post=3148"}],"curies":[{"name":"\u304a\u75b2\u308c\u69d8\u3067\u3057\u305f","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}